Product

Gas insulated load breaker switch

SF6 Gas Insulated Load Break Switches are installed on overheadline. Used to divide, make, and break lines in cities to provide a stable power supply.

FEATURE
  • Front and bottom On/OFF indicator
  • Hermetically sealed enclosure
  • Overpressure relief device
  • Manual locking device
  • Low gas presure interlock device
  • Sectionalizer function
HiGH RELIABILITY
  • Simple operating mechanism
  • Switchgear vessel made of stainless steel
  • Climate-independent
  • Easy installation and operation
  • Pure puffer techniques, no leakage current between open gap
SPECIFICATIONS
SPECIFICATIONS detail
Maximum system Voltage (kV) 15 27 36
Norminal frequency (Hz) 50 / 60 50 / 60 50 / 60
Rated continuous current (A) 630 630 630
Short time withstand current (kA) 12.5 / 16 12.5 / 16 12.5 / 16
Fault make capacity (RMS) (kA) 12.5 / 16 12.5 / 16 12.5 / 16
Fault make capacity (Peak) (kA) 32.5 / 41.6 32.5 / 41.6 32.5 / 41.6
Mechanical endurance 5000 5000 5000
Load switching (A) 630 630 630
Line charging switching (A) 1.5 1.5 1.5
Cable charging switching (A) 25 25 25
Lighting impulse withstand level (kV/BIL) 110 150 170